BS 7671
From Wikipedia the free encyclopedia
Electrical installations |
---|
Wiring practice by region or country |
Regulation of electrical installations |
Cabling and accessories |
Switching and protection devices |
British Standard BS 7671 "Requirements for Electrical Installations. IET Wiring Regulations", informally called in the UK electrical community "The Regs", is the national standard in the United Kingdom for electrical installation and the safety of electrical wiring systems.[1]
It did not become a recognized British Standard until after the publication of the 16th edition in 1992. The standard takes account of the technical substance of agreements reached in CENELEC.[2]
BS 7671 is also used as a national standard by Mauritius, St Lucia, Saint Vincent and the Grenadines, Sierra Leone, Singapore, Sri Lanka, Trinidad and Tobago, Uganda, Cyprus, and several other countries, which base their wiring regulations on it.
The latest version is BS 7671:2018+A3:2024 (18th Edition, amendment 3) issued in 2024.
Scope
[edit]Locations
[edit]The regulations in BS7671 apply to the design, selection, erection and verification of electrical installations within:
- residential properties
- commercial properties
- public premises
- industrial premises
- prefabricated building
- low voltage generating sets
- highway equipment and street furniture
- locations containing a bath or shower
- rooms or cabins that contain a sauna
- swimming pools and other basins
- construction and demolition sites
- agricultural and horticultural premises
- caravan/camping parks and similar locations
- marinas and similar locations
- medical locations
- exhibitions, shows and stands
- Solar photovoltaic (PV) power supply systems (Domestic and commercial)
- outdoor lighting installations
- extra-low voltage lighting
- mobile and transportable units
- caravans and motor caravans
- temporary installations for structures, amusement devices/booths at fairgrounds, amusement parks, circuses and professional stage and broadcast applications
- operating and maintenance gangways
- floor and ceiling heating systems
- onshore units of electrical shore connections for inland navigation vessels.
Exclusions:
- systems for the distribution of electricity to the public other than prosumer installations covered by Chapter 82
- railway traction equipment, rolling stock and signalling equipment
- equipment of motor vehicles, except those to which the requirements of the Regulations concerning caravans or other types of mobile unit are applicable
- equipment onboard ships covered by BS 8450, BS EN 60092-507, BS EN ISO 13297 or BS EN ISO 10133
- equipment of mobile or fixed offshore installations
- equipment within and aircraft[vague]
- those aspects of mines covered by Statutory Regulations
- radio interference suppression equipment, except so far as it affects safety of the electrical installation
- lightning protection systems for buildings and structures covered by BS EN 62305
- those aspects of Lift Installations covered by relevant parts of BS 5655 and BS EN 81 and those aspects of escalator or moving walkway installations covered by relevant parts of BS 5656 and BS EN 115
- electrical equipment of machines covered by BS EN 60204
- electric fences covered by BS EN 60335-2-76
- the DC side of cathodic protection systems complying with the relevant part(s) of BS EN 12696, BS EN 12954, BS EN ISO 13174, BS EN 13636 and BS EN 14505.
Voltages
[edit]BS 7671 only covers electrical systems with the following characteristics:
- having a nominal voltage up to but not exceeding 1000V AC or 1500V DC
- for AC having a supply frequency of 50, 60 or 400Hz, though the use of other frequencies for special purposes is not excluded.
This includes low-voltage installations, as found in most domestic and commercial properties, and extra-low-voltage systems, but excludes high voltage, as found in generation, transmission and distribution networks.
Compilation and publication
[edit]The standard is maintained by the Joint IET/BSI Technical Committee JPEL/64, the UK National Committee for Wiring Regulations, and published jointly by the IET (formerly IEE) and BSI. Although the IET and BSI are non-governmental organisations and the Wiring Regulations are non-statutory, they are referenced in several UK statutory instruments, and in most cases, for practical purposes, have legal force as the appropriate method of electric wiring.[3]
The BSI (British Standards Institute) publishes numerous titles concerning acceptable standards of design/safety/quality across different fields.
History of BS 7671 and predecessor standards
[edit]The first edition was published in 1882 as the "Rules and Regulations for the Prevention of Fire Risks arising from Electric Lighting." The title became "General Rules recommended for Wiring for the Supply of Electrical Energy" with the third edition in 1897, "Wiring Rules" with the fifth edition of 1907, and settled at "Regulations for the Electrical Equipment of Buildings" with the eighth edition in 1924.
Since the 15th edition (1981), these regulations have closely followed the corresponding international standard IEC 60364. In 1992, the IEE Wiring Regulations became British Standard BS 7671 so that the legal enforcement of their requirements was easier both with regard to the Electricity at Work regulations and from an international point of view.[4] They are now treated similar to other British Standards. BS 7671 has converged towards (and is largely based on) the European Committee for Electrotechnical Standardization (CENELEC) harmonisation documents, and therefore is technically very similar to the current wiring regulations of other European countries.
Timeline
[edit]The historical timeline of publication can be found within documents published by the IET, such as within the PDF detailing amendment 3 to the 18th edition ([5]), and is summarised below, along with some notable other events. Only major changes between editions/amendments are noted.
Year | Ed. | Pub. | Notes |
---|---|---|---|
1882 | 1st | IEE | Entitled ‘Rules and Regulations for the prevention of Fire Risks Arising from Electric Lighting’, and known as the "Wiring Rules". Two core cable, line and neutral, no earth. Protection was a re-wirable fuse. |
1888 | 2nd | IEE | Entitled 'Wiring Rules & Regulations in Buildings.[verification needed] |
1897 | 3rd | IEE | Entitled ‘General Rules recommended for Wiring for the Supply of Electrical Energy’. |
1903 | 4th | IEE | |
1907 | 5th | IEE | Entitled ‘Wiring Rules’. |
1911 | 6th | IEE | |
1916 | 7th | IEE | |
1924 | 8th | IEE | Entitled ‘Regulations for the Electrical Equipment of Buildings’. |
1927 | 9th | IEE | |
1934 | 10th | IEE | Three-phase colours changed to red, white and green; neutral or earth to black. |
1939 | 11th | IEE | Last edition to allow sockets in a bathroom. Three-phase colours changed to red, white and blue; black for neutral or earth. Revised in 1943; reprint with minor amendments in 1945; supplement issued in 1946; revision to section 8 in 1948. |
1950 | 12th | IEE | Three-phase colours of red white and blue; black for neutral or earth in fixed wiring; green earth in flex. Supplement issued 1954. First mention of PVC insulated cables. |
1955 | 13th | IEE | Reprinted in 1958, 1961, 1962, 1964. |
1966 | 14th | IEE | Added earthing on lighting circuits. Reprinted with amendments in 1968 and 1969, a supplement was issued 'on use in metric terms' in 1969, amended and reprinted 'in metric units' in 1970, reprinted in 1972 and 1973, amended and reprinted 1974 and 1976. |
1981 | 15th | IEE | Entitled 'Regulations for Electrical Installations'. Issued with red cover. Amended and reprinted in 1983 (green cover), 1984 (yellow cover), amended in 1985, amended and reprinted in 1986 (blue cover; to remove voltage operated earth leakage circuit breakers), 1987 (brown cover), and finally just reprinted with minor corrections (no amendment) in 1988 (brown cover). |
1991 | 16th | IEE | Issued with red cover. Reprinted with minor corrections in 1992 (red cover), then again in the same year retitled as 'Requirements for Electrical Installations BS 7671:1992' (red cover; see next entry). Amended (no. 1) and reprinted in 1994 (green cover), 1997 (no. 2; yellow cover), and amended again (no. 3) in 2000. Then reissued as BS 7671:2001 in 2001 (blue cover), and amended further (no. 1) in 2002 and amended again (no. 2) and reprinted in 2004 (brown cover). The 2004 amendment saw major changes to wire colouring, following European-wide harmonisation efforts. Quoting the amendment document:[6]
|
1992 | - | - | The IEE wiring regulations were adopted by the British Standards Institute as BS 7671. |
1992 | - | - | The Electricity at Work Regulations legislation come fully into effect in Northern Ireland.[verification needed] |
2002 | - | - | The Electricity Safety, Quality and Continuity Regulations 2002 (legislation) required consumer electrical installations incorporating generators operating in parallel with the grid, or as a switched alternative to the grid, to conform to BS 7671 (Regulations 21 and 22). |
2004 | - | - | Part P of the Building Regulations ("Requirements for Electrical Installations") came into force, covering legal requirements for domestic electrical installations in England and Wales. The guidance in the accompanying Approved Documents refers explicitly to BS 7671 as being one way to achieve compliance. |
2006 | - | - | The IEE merged with the IIE to form the IET. |
2008 | 17th | IET/BSI | First new edition to be published by the IET (jointly with the BSI). RCDs were now required for most outlets in domestic premises or otherwise for general use by unskilled persons. Issued with red cover. Amended (no. 1) and reprinted in 2011 (green cover), amended (no. 2) Aug 2013, amended (no. 3) and reprinted 2015 (yellow cover). Amendment 1 replaced Periodic inspection reports (PIRs) with Electrical Installation Condition Reports (EICRs), a section on surge protection devices (SPDs) was introduced, and some details relating to medical locations were added.[7] Amendment 2 added a new section on electric vehicle charging.[8] Amendment 3 introduced requirements for the use of non-combustable consumer units (or enclosures) in domestic premises, along with use of metal wiring/containment clips in certain situations, and expanded use of RCDs into commercial/industrial spaces.[9] New sections have been added relating to microgeneration and solar photovoltaic systems[verification needed], and breakers (including high resilience breaker layout).[verification needed] |
2018 | 18th | IET/BSI | Introduced energy efficiency performance levels and the use of surge protection devices and arc fault detection devices.[10] Issued with blue cover. Amended February 2020 (no. 1), changing rules on car charging. Amended (no. 2) and reprinted March 2022 (brown cover). Amended (no. 3) July 2024, introducing the concept of bi-directional vs. uni-directional protective devices in response to issue of how existing devices were being used for prosumer power generation circuits. |
See also
[edit]- British Standards
- Electrical code
- Electrical wiring
- Electrical wiring (UK)
- IEC 60364
- Earthing system
References
[edit]- ^ BS7671 chapter 11 - scope
- ^ BS7671: Preface
- ^ "Regulatory Requirements" (PDF). p. 3.
- ^ Electrician's guide to the 17th edition of the IEE wiring regulations. 3rd edition pub 2012 John Whitfield
- ^ Introduction to Amendment 3:2024 (PDF), IET Electrical, retrieved 29 September 2024
- ^ "Amendment No 2 : 2004 to BS 7671 : 2001". Archived from the original (PDF) on 2 May 2006. Retrieved 3 October 2024.
- ^ "17th Edition (BS 7671:2008) incorporating Amendment No 1" (PDF). Retrieved 29 September 2024.
- ^ "17th Edition Amendment 2". Retrieved 29 September 2024.
- ^ "17th Edition Amendment 3 – What You Need to Know". Retrieved 29 September 2024.
- ^ Whitton, Nicole (2016). "BS 7671: the 18th Edition report". electrical.theiet.org. IET Electrical. Retrieved 8 February 2018.